Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 5/26/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be displayed in the elevator machine room. 5/26/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 5/26/2022
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Could not get elevator to revert back to normal operation from fire service operation. Take corrective action as needed. 12/29/2023
MO Minimum : Elevators (I) - Pits (I)1 The pit has around 14" of water in it. The pit shall be kept clean and dry and water and oil shall not be allowed to accumulate on pit floors.
MO Minimum : Elevators (I) - Pits (I)1 Water and oil shall not be allowed to accumulate on pit floors. Note: The pit has at least 12" of water in it. 10/12/2022