Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers x The sump pump shall have a cover installed. 6/15/2022
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2 through 2.27.8 Firefighter Service x x All phases of fire service and all fire service initiating devices shall be tested. 6/15/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state operating certificate onsite 10/26/2023
A17.1-2016 : Elevators 1.3 - Operating control devices 8.10.2.2.1(c) x Finish all hallway walls and install install hallway fixture. 6/15/2022
A17.1-2016 : Elevators 1.4 - Sills and car floor 8.10.2.2.1(d) x The cab flooring shall be installed. 6/15/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.10.2.2.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 6/15/2022
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.10.2.2.1(o) x Install all signage. 6/15/2022
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.10.2.2.2(l) x An ABC type fire extinguisher shall be mounted at the 7th floor near the elevator door as the controller is located in the jamb at the 7th floor. 6/15/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4 Instructions for Locating Maintenance Records x A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 6/15/2022
A17.1-2016 : Elevators 3.10 - Hoistway construction 8.7.2.1.1 Hoistway Enclosure Walls x Seal all penetrations in the hoistway. 6/15/2022