Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods 8.6.5.8 - Need to determine if this unit is a single bottom jack. If unit is a single bottom type, corrective action shall be taken. If it is determined this unit is not a single bottom type, documentation shall be kept on-site for elevator personnel to confirm. 7/23/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 7/23/2021
conversion conversion n/a Back wall needs to be refastened to cab floor. 8/21/2018
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Emergency power operation of the elevator shall be tested to determine conformance with the applicable requirements. 7/9/2021
conversion conversion n/a Top car inspection station shall work. 8/21/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 7/23/2021