Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone in cab is not working. Re-inspection required 1/31/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 Repair door knob on machine room. 10/19/2020
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Inadequate light in front of car #1 in machine room. 1/27/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 Repair machine room wall and fire caulk. 1/27/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 Repair door handle on door leading to machine room. 1/27/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The following tests need to be performed to complete 5 year inspection: full load, full load car safeties, full load, full speed car buffer, counterweight buffer, 125% brake, overspeed governor jaw and switch speeds, overspeed governor pull thru, car safeties pull out. Re-inspection required 3/26/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No current certificate in machine room. 1/27/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display updated operating certificate in machine room. 10/19/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 3/11/2024